DAX 420

The DAX 420 detector was designed to continuously measure the presence of various explosive gases in the air. Its measurement principle, catalytic combustion, gives it its major benefits: - very short response time, - accuracy and reliability of measurements. By connecting it to a Dalemans unit or to any other instrument that can receive a 4..20 mA signal, you will benefit from a highly flexible installation. ATEX certified, this detector is especially suitable for the industrial sector, whose applications are located in an explosive atmosphere.

Benefits and advantages of the DAX 420

  • Continuous explosive gas detection: Monitors the presence of combustible gases such as methane, propane, hydrogen and acetylene using catalytic sensor technology.
  • Fast and reliable response: Offers a response time of less than 30 seconds and a measurement range of 0–100% of the Lower Explosive Limit (LEL).
  • ATEX protection for industrial environments: Certified for use in the specified hazardous areas, including Zones 1 and 2 for gases.
  • Integration via analogue signal: Features a 4–20 mA output compatible with Dalemans control panels and other devices capable of receiving this signal.
  • Robust construction for demanding conditions: Features an AISI 316L stainless steel sensor head, an IP6X protection rating and an operating temperature range of −20 °C to +55 °C.
MODEL DAX 420
SENSING HEAD Stainless steel 1.4404 (AISI316L)
SINTERED METAL FILTER
JUNCTION BOX Aluminium
DIMENSIONS / WEIGHT 193 x 145 x 90 mm / 1.500 g
SENSOR TYPE / OUTPUT SIGNAL Catalytic (Pellistor) / 3-wire 4..20 mA current loop
ADJUSTMENTS Zero and calibration by internal potentiometers
MEASURING RANGE 0 - 100 % LEL
RESOLUTION ± 3% full scale < 60% LEL ± 3% full scale < 60% LEL
RESPONSE TIME (T90) < 30 sec.
EXPECTED OPERATING LIFE SPAN > 2 years
SUPPLY VOLTAGE 19 - 30 Vdc
SUPPLY CURRENT* Max. 90 mA
STORAGE TEMPERATURE -40ºC to +80ºC
TEMPERATURE RANGE -20ºC to +55ºC
AMBIENT HUMIDITY 20 - 90 % HR
INTERMITTENT HUMIDITY 10 - 99 % HR
PRESSURE 90 - 110 kPa
CABLE CROSS SECTIONAL AREA 0.75 - 2.5 mm2 (solid wires)
MAX. CABLE LENGTH 1.000 m
LOOP RESISTOR 50 - 750 ohms
INGRESS PROTECTION IP 6X (dust tight)
CABLE ENTRIES 1 x M20 / 6.1 - 11.7 mm (other size upon request)
HAZARDOUS AREAS Zones 1 or 2 (gas) - Zones 21 or 22 (dust)